ÇöÀçÀ§Ä¡ : Home >  >  > 
AE212501 Power Quality Logger
            
	 
     
     
     
|  | 
| Portable, compact unit – plugs into standard US 120V outlets, Simple operation: Plug in, Record etc. | 
| 
SPECIFICATIONS
| 
| Features  |  
| 
Portable, compact unit – plugs into standard US 120V outlets 
Simple operation: Plug in, Record, Download and Read 
Measures & stores electrical parameters: V, A, Hz and more 
Measures and stores power parameters: W, VA, Var, Demand, Peak Demand and more 
Measures and stores power quality parameters: Harmonics, THD (rms and fundamental), K-Factor & more 
Automatically captures worst-case Surge, Sag & THD waveforms for voltage & current 
Stores 100 worst case surge & sag events including time, date & duration 
High accuracy & resolution: 128 samples/cycle, 16 bit resolution 
LEDs indicate mode of operation 
Records up to 12 data channels 
Powered from voltage input channel 
Battery backup data integrity during power outages for up to 1 year. Configuration in non-volatile memory 
Optically isolated RS-232 output for direct connection to a PC 
EN 1010, 150V, Cat. III 
Includes DataView¢ç Lite Analysis and Reporting Software DataView¢ç Lite and Professional Data Analysis & Reporting Software  |  
|  |  
| Software Features  |  
| 
Display and analyze data on your PC 
Configure all data logger functions and parameters from your PC including sample rate, recording length, channel configuration & more 
Customize frames, templates & reports to your exact needs 
Display real time data on your PC & download previously recorded data 
Create & store a complete library of configurations that can be uploaded to the logger as needed 
Zoom in and out and pan through sections of the graph to analyze the data 
Display waveforms, trend graphs, harmonic spectrums and text summaries 
Display surge and sag events in high-resolution waveforms and as tabular listings  |  
|  |  |  
| Models | AE212501 | AE212502 | AE212503 | AE212504 |  
| (Memory) | (128KB) | (1MB) | (128KB) | (1MB) |  
| Electrical Specifications |  
| Measurements | True RMS measurement. 128 samples are simultaneously taken for voltage and current channel |  
| Voltage |  
| Range | 0 to 140V |  
| Resolution | 0.1V |  
| Accuracy | ¡¾(0.3% of Reading + 0.3V) |  
| Current |  
| Range | 0 to 15A (70A peak maximum) |  
| Resolution | 0.01A |  
| Accuracy | ¡¾(0.5% of Reading + 0.03A) @ 0.75A to 15A ¡¾0.30A @ < 0.75A |  
| Frequency (Hz) |  
| Range | 45 to 65Hz |  
| Resolution | 0.01Hz |  
| Accuracy | 0.1Hz |  
| Harmonics |  
| Range | Up to 50th for both Voltage & Current |  
| Resolution | 0.1V for Voltage & 0.1A for Current |  
| Power - Watt/ VA/Var |  
| Range | 0 to 2.1K Watt or VA or Var |  
| Resolution | 0.1W, 0.1VA, 0.1Var |  
| Accuracy | ¡¾(2.0% of Reading + 4x), where x is Watt or VA or Var |  
| Power & Power Factor |  
| Resolution | 0.01 |  
| Accuracy | ¡¾0.03% @ PF/DPF = 1 |  
| Programmable Parameters |  
|  | V, A, Hz, Odd & Even Harmonics( V & A), W, VA, Var, THD (V & A), PF, DF, K-Factor |  
| Demand | VA, W (10/15/30 minutes or user-definable) |  
| Peak Demand | Over demand period |  
| Voltage Sag/Surge | User-definable magnitude |  
| Input |  
| Input Channels | 1 Voltage/1 Current |  
| Sample Rate | 128 per cycle per channel |  
| Recording |  
| Storage Rate | 125ms to 7 days |  
| Recording Session Length | 15 minutes to 8 weeks (user programmable) |  
| Total Memory | 128KB | 1MB | 128KB | 1MB |  
| Date and Time | MM/DD/YY hh/mm/ss.sss |  
| Surge & Sag andTHD Waveform
 Storage
 (worst case)
 | 5THD Waveform
 | 20THD Waveform
 | 5THD Waveform
 | 20THD Waveform
 |  
 
| CAT NO. |  | MODEL |  | DEscRIPTION |  | AVAIL |  | PRICE |  
| AE212501 |  | PQL 100 |  | Power Quality Logger (128KB storage) |  | Yes |  | 1,717,200 |  
| AE212502 |  | PQL 120 |  | Power Quality Logger (128KB storage) |  | Yes |  | 1,717,200 |  
| AE212503 |  | PQL 100 |  | Power Quality Logger (w/optional 1MB storage) |  | Yes |  | 1,933,200 |  
| AE212504 |  | PQL 120 |  | Power Quality Logger (w/optional 1MB storage) |  | Yes |  | 1,933,200 |  
| AE211902 |  | ¡¡ | ¡¡ | OPTIONAL Soft Carrying Case FOR Power Quality Loggers |  | Yes |  | 32,400 |  |  | 
 
    
    »ç¿ëÈı⠸®½ºÆ®
    
        
        
    
    
        
            | Á¦¸ñ | Æò°¡ | 
    
    
    
            | ÀÌ »óǰ¿¡ ´ëÇÑ »ç¿ëÈıⰡ ¾ÆÁ÷ ¾ø½À´Ï´Ù. »ç¿ëÈı⸦ ÀÛ¼ºÇØ ÁÖ½Ã¸é ´Ù¸¥ ºÐµé²² ¸¹Àº µµ¿òÀÌ µË´Ï´Ù.
 | 
    
    
    * ÀÌ »óǰÀ» »ç¿ëÇØ º¸¼Ì´Ù¸é »ç¿ëÈı⸦ ½á ÁֽʽÿÀ. Æò°¡Çϱâ
    
    
	
 
	
	»óǰ¹®ÀÇ ¸®½ºÆ®
	
		
		
	
	
		
	        | Á¦¸ñ | ´äº¯ | 
	
	
	
		| ÀÌ »óǰ¿¡ ´ëÇÑ Áú¹®ÀÌ ¾ÆÁ÷ ¾ø½À´Ï´Ù. ±Ã±ÝÇϽŠ»çÇ×Àº À̰÷¿¡ Áú¹®ÇÏ¿© ÁֽʽÿÀ.
 | 
	
	
	* ÀÌ »óǰ¿¡ ´ëÇÑ ±Ã±ÝÇÑ »çÇ×ÀÌ ÀÖÀ¸½Å ºÐÀº Áú¹®ÇØ ÁֽʽÿÀ.
	¹®ÀÇÇϱâ
	
	
	
 
|  | 
| ÀÌ »óǰ°ú °ü·ÃµÈ »óǰÀÌ ¾ø½À´Ï´Ù. |