High accuracy ¡¾1% FS, Ruggedly constructed cases for years of field use, Lightweight portability
• Now offering a premier line of 40, 50, and 60 kV models, providing test voltages for a wide range of electrical equipment • Featuring 3 1/2 digit, digital LCD display output voltmeter and currentmeter for easy reading even in direct sunlight • High accuracy ¡¾1% FS • Ruggedly constructed cases for years of field use • Lightweight portability • Zero start (safety interlock feature) • Output termination: toroid with output lead • Adjustable overcurrent trip from 10% to 70% of rating • Internal short circuit protection
PX299640
40 kV AC, 10 mA hipot designed primarily for vacuum bottle testing; however, it can be used for testing breakers, switchgear, and many other apparatus
One-piece portability for field testing
Lightweight (56 lbs., 25 kg)
Emergency Off pushbutton
Guard ground circuit
PX299650
50 kV AC hipot, multi-purpose, rugged design; tests breakers, switchgear, and many other apparatu
40 mA of output current independent of test specimen type (resistive or capacitive)
Two-piece construction
External interlock provision
CE marked 650-2P version available
PX299660
60 kV AC hipot designed primarily for vacuum bottle testing and field use; however, it can be used for testing breakers, switchgear, and many other apparatus
Tests up to 24.9 kV class interrupters in accordance with ANSI/IEEE C37.60 specifications
Portable two-piece unit
Digital dwell timer
Selectable rate of voltage rise (500 volts/sec, 3000 volts/sec)
Failure indicator with reset switch
Automatic voltage control
Digitally programmable set-point eliminates test voltage overshoot as found with meter relay type voltage control
Memory feature included in output voltmeter to record breakdown voltage. Reset switch clears unit after failure occurs
Single-ended high voltage transformer develops 0-60 kV AC with respect to ground potential
10 mA of output current independent of test specimen type (resistive or capacitive)
External interlock provision
SPECIFICATIONS
Model
PX299650
PX299640
PX299660
Input
120 VAC, 60 Hz, single phase, 2 kVA, 20 A Or 220 VAC, 50 Hz, singe phase, 2 kVA, 11 A
120 or 220 VAC, 50/60 Hz, single phase, 400 VA, 5 A
120 VAC, 50/60 Hz, single phase, 6 A Or 220 VAC, 50/60 Hz, single phase, 3 A
Output
0-50 kV AC, 40 mA
0-40 kV AC, 10 mA
0-60 kV AC (single ended), 10 mA
Duty Cycle
5 min ON / 15 min OFF @ 40 mA
120 Volt 20 min ON / 30 min OFF @ 10 mA 220 Volt 15 min ON / 45 min OFF @ 10 mA
5 min ON / 15 min OFF @ 10 mA
Distortion
Less than 5%
Less than 5%
Less than 5%
Output Termination
Output lead
Output lead
Output lead
Metering
Single range voltmeter: 0-50 kV AC Single range ammeter: 0-40 mA
Single range voltmeter: 0-40 kV AC Single range ammeter: 0-10 mA
Single range voltmeter: 0-60 kV AC Single range ammeter: 0-10 mA
Timer
—
—
1-999 seconds
Dimensions & Weight
Controls
Controls
Controls
16.5" W x 15.25" D x 11.25" H (419 mm x 388 mm x 286 mm) 31 lbs. (14 kg)
18.5" W x 10.75" D x 19.5" H (464 mm x 273 mm x 495 mm) 56 lbs. (25 kg) (120 Volt unit)
16.5" W x 15.25" D x 11.25" H (419 mm x 388 mm x 286 mm) 31 lbs. (14 kg)
HV Transformer
HV Transformer
15" W x 15" D x 16.5" H (381 mm x 381 mm x 419 mm) 79 lbs. (36 kg)