UM831011 Calibrator with carrying case,batteries

Á¦Á¶»ç : DAVIS
½ÃÁß°¡°Ý : ¿ø
ÆǸŰ¡°Ý  : ¿ø
Æ÷ÀÎÆ® : Á¡
¼ö·® :
  PLUS   MINUS   °³
¡á ȸ¿ø°¡ÀÔÀ» ÇϽøé ÇÒÀεȰ¡°ÝÀ» º¸½Ç¼ö ÀÖ½À´Ï´Ù.
¡á ¸ðµç°¡°ÝÀººÎ°¡¼¼º°µµ ÀÔ´Ï´Ù.
¡á ȸ¿øÀÌ µÇ½Ã¸é °¡°Ýº¯µ¿Á¤º¸, ½ÅÁ¦Ç°, ƯÆÇÁ¦Ç°, ±â¼úÁ¤º¸µî ´Ù¾çÇÑ
´º½ºÁ¤º¸¸¦ º¸³»µå¸³´Ï´Ù.
¡á 30¸¸¿ø¹Ì¸¸Àº Åùèºñ 3,000¿ø(ÂøºÒ)ÀÔ´Ï´Ù.
¡á Ä«µå°áÀç½Ã ¼¼±Ý°è»ê¼­ ¹ßÇà ºÒ°¡ÇÕ´Ï´Ù.
¡á ¹è¼ÛÀº Æò±Õ 2~3ÀÏÁ¤µµ ¿¹»óµË´Ï´Ù.

»ó¼¼ÆäÀÌÁö¸¦ ¸¶ÀÌÇÇÇ÷Πº¸³»±â - À¥¿ë »ó¼¼ÆäÀÌÁö¸¦ twitter·Î º¸³»±â »ó¼¼ÆäÀÌÁö¸¦ facebookÀ¸·Î º¸³»±â »ó¼¼ÆäÀÌÁö¸¦ Me2Day·Î º¸³»±â

Features
  • Sources and reads milliamps
  • Simulates 2-wire transmitters
  • Powers and reads 2-wire transmitters
  • Reads and simulates dp-transmitters in percent flow
  • Fixed Calibration currents
  • Auto-stepping for handsfree calibration
  • Auto-ramp cycling for endurance tests
  • Fixed currents for valve stroking
 

¡¡

UM831011 can power (24VDC) and read 2-wire transmitters to perform field calibration. Output currents are adjustable with a 10 microamp resolution in both source and transmitter simulation mode.¡¡
 FIXED STEPS The calibrator can source or simulate fixed calibration currents to test or calibrate receivers and to stroke valves. Different current levels are obtained from a menu.
4-20mA lin 4 - 8 - 12 - 16 - 20mA   ¡¡ ¡¡ ¡¡
0-20mA lin 0 - 5 - 10 - 15 - 20mA   ¡¡ ¡¡ ¡¡
4-20mA sq.rt (flow) 4 - 5 - 8 - 13 - 20mA   ¡¡ ¡¡ ¡¡
0-20mA sq.rt (flow) 0 - 1.25 - 5 - 11.25 - 20mA   ¡¡ ¡¡ ¡¡
4-20mA valve 3.8 - 4 - 4.2 - 12 - 19 - 20 - 21mA
 Output currents can be changed manually or automatically. Time between steps is 10 seconds in the auto-stepping mode.
In the valve series, auto-stepping will be
  3.8 - 4 - 4.2   or   19 - 20 - 21mA
RAMPING The calibrator can source or simulate with high resolution a continuous up/down cycling between 4 and 20mA or 0 and 20mA.
The travel time between limits is 60 seconds.
 READING IN PERCENT The calibrator can display readings in percent of a 4-20mA or 0-20mA span.
Unit also reads or simulates dP-transmitters directly in percent of flow.

SPECIFICATIONS

Output range

0-21.00 mA
Input range 0-21.00 mA
Accuracy 0.05% of range
Resolution 10 microamps
Temperature effect 0.003% ¡Æ/C, 0.0015% ¡Æ/F
Internal loop power 24 VDC stabilized
External loop power 56 VDC max.
Measurement input 12 Ohms including fuse
Drive capability 900 Ohms
Operating temp. -10¡ÆC to +50¡ÆC, 14¡ÆF to 122¡ÆF
Battery life Sources 12 mA 13 hours
Measures 64 hours
Batteries 1.5V 4 x R6, AA (Penlite)
Loop mismatch Flashes "LOOP"
Low battery Flashes "LOBAT"
Overrange Flashes "EEEE"
Reversed polarity Flashes "POL"
Adapter line/6 VDC P/N 13700 230V/50Hz
P/N 13602 70V/60Hz
Housing High impact ABS
Size 3" x 5" x 0.83"
77 x 124 x 21mm
Weight 285 grams/9 oz Includingbatteries

CAT NO. MODEL DEscRIPTION AVAIL PRICE 
UM831011   UPS-II   SMART LOOP CALIBRATOR FOR MILLIAMPS   Yes   872,100
UM831012   UPS-iS   INTRISICALLY SAFE LOOP CALIBRATOR   Yes   1,643,220
UM831013   191-A003   OPTIONAL 70V/60Hz POWER SUPPLY FOR UPS-II 13602 (P/N: 191-A003) FOR Smart Loop Calibrators   Yes   82,620