These recorders are designed with the latest innovation in recording technology, enclosures and functionality. Finding a place to install this recorder is easy, with its compact 2.5" panel depth and short 1.3" protrusion from the front of the panel. It can be panel or surface mounted. The cutout size is the commonly utilized 12.7" square cutout.
Features
1 or 2 trend pen versions
4 digit red LED display
High/Low limit capability available
Universal Inputs
Up to 2 alarms per pen
Universal power supply
Communications
SPECIFICATIONS
Recording
Pen Type
Disposable fiber tip
Pen Color
Pen 1 - Red
Pen 2 - Green
Chart Size
10 inch
Chart Drive
Stepper motor
Chart Rotation
User configurable; 8 hour, 12 hour, 24 hour or 7 day
Chart Span
Bottom and top of span, -9999 to 9999 units
Inputs
Input Types/Range
Type
Range
Thermocouple
J
0¡ÆC to 70¡ÆC
0¡ÆF to 1400¡ÆF
K
0¡ÆC to 1360¡ÆC
0¡ÆF to 2500¡ÆF
T
-200¡ÆC to 400¡ÆC
-330¡ÆF to 750¡ÆF
R
200¡ÆC to 1650¡ÆC
400¡ÆF to 3000¡ÆF
S
200¡ÆC to 1650¡ÆC
400¡ÆF to 3000¡ÆF
RTD
100 ohm
-140¡ÆC to 400¡ÆC
-220¡ÆF to 750¡ÆF
Platinum
¡¡
.00385 ohms/ohm/¡ÆC
¡¡
Current DC
0 to 20mA, 4 to 20mA
Internal 4.7 ohm Shunt Resistor
Voltage DC
0 to 25mV, 0 to 50mV, 10 to 50mV, 0 to 5 V, 1 to 5 V
Input Performance
Performance Under Reference Condition
Measurement Error
Type J, K, T, R, S and RTD: ¡¾0.25% of span ¡¾1 degree mA, mV and VDC: ¡¾0.25% of scaled span plus 1 least significant digit
Cold Junction Compensation Error
¡¾0.2¡ÆC @ 25¡ÆC
Cold Junction Compensation Rejection
0.04¡Æ/¡ÆC deviation from 25¡ÆC
Linearization Error expectations
TCs: ¡¾0.25¡ÆC typical, ¡¾0.5¡ÆC worst case with RTDs: ¡¾0.1¡ÆC typical, ¡¾0.3¡ÆC worst case
Ambient Temperature Error
¡¾0.01% of span per ¡ÆC deviation from 25¡ÆC
Power Requirements
Line Voltage
90-264 VAC, 50/60 Hz
Power Consumption
18 VA Maximum
Construction
Enclosure
Injection molded Noryl case and cover with acrylic window
NEMA Rating
NEMA 3 standard
Mounting
Panel or wall
Overall Dimensions
14" wide x 14" high x 3.8" deep (355.6mm x 355.6mm x 96.5mm)
Panel Cutout
12.7" wide x 12.7" high (322.58mm x 322.58mm)
Panel Depth
2.5" (63.5mm)
Panel Protrusion
1.3" (33.0mm)
Weight
15 lbs maximum
Alarms
Number
Up to two process alarms for each of two inputs
Type
Process high or low
Limit Device output
Optional high/low limits for each input with latching
Normally open output latches open
Red reset button included to the right of the display
Hysteresis
Fully adjustable, 0 to 200 units, single sided
Security
Alarm setpoint changes can be prohibited
Sensor Fault Action
Alarms work normally in "Hi" and "Lo" conditions
Relay Outputs
Relays
SPDT, contacts rated 5 amps resistive at 115 VAC, 2.5amps resistive at 230 VAC, 1/8 HP at 230 VAC (singlephase), 250 VA at 115/230
¡¡
CAT NO.
MODEL
DEscRIPTION
AVAIL
PRICE
PL1487301
51000011
1 Channel Recorder NEMA 3 Case with Alarms/Relays
Yes
1,198,908
PL1487311
5700011
2 Channel Recorder NEMA 3 Case with Alarms/Relays
Yes
1,624,860
PL148732
54020011
1 CH.REC. NEMA 3 CASE W/ALARMS2 RELAY OUTPUTS
Yes
1,551,420
PL148733
54422011
2 CH.REC. NEMA 3 CASE W/ALARMS2 RELAYS OUT PER CH. 54422011