Accurate, reliable current measurement over a wide frequency range,Input/output isolation
Features
Accurate, reliable current measurement over a wide frequency range
Input/output isolation
Applications
Designed to withstand motor start-up transients
SPECIFICATIONS
INPUT
Frequency Range
50 to 400Hz
Burden
1.0VA F.S
Current Overload 2 times full scale rating (continuous), except 20A model. 20A model: 1.25 times full scale rating 50 times full scale (1 Sec. transient) Dielectric Test (Input/Output/Case)1500VAC
OUTPUT
Output Ripple
Less than 1.0%F.S.
Response
400 milliSeconds
Output Loading (Ω)
0-1mA
0-10K
4-20mA
0-1500
Field Adjustable Cal
±10%
ACCURACY
±0.25%F.S. (internal sensor)
±0.5%F.S. (external sensor)
Includes effects of linearity
0.5%F.S. over frequency range (typical.)
Temperature Effect
(-20°C to 60°C)
±1.0%RDG
Instrument Power (STD. 4-20mA Units)
85-135VAC, 50-70Hz
Units also available with 4-20mA loop powered (15-40VDC), 0-10VDC and 0-5VDC Outputs. Please inquire. Case dimensions and connection diagrams available upon request.
CAT NO.
MODEL
DEscRIPTION
AVAIL
PRICE
051286
CT5-005E
AC CURRENT TRANSDCR (4-20mA OUTPUT/1 INPUT)
Yes
345,600
051291
CT5-100E
AC CURRENT TRANSDCR (4-20mA OUTPUT/1 INPUT)
Yes
486,000
051295
CT5-500E
AC CURRENT TRANSDCR (4-20mA OUTPUT/1 INPUT)
Yes
486,000
051298
CT5-1000E
AC CURRENT TRANSDCR (4-20mA OUTPUT/1 INPUT)
Yes
486,000
사용후기 리스트
제목
평가
이 상품에 대한 사용후기가 아직 없습니다.
사용후기를 작성해 주시면 다른 분들께 많은 도움이 됩니다.