Accurate, reliable current measurement over a wide frequency range,Input/output isolation
Features
Accurate, reliable current measurement over a wide frequency range
Input/output isolation
Applications
Designed to withstand motor start-up transients
SPECIFICATIONS
INPUT
Frequency Range
50 to 400Hz
Burden
1.0VA F.S
Current Overload 2 times full scale rating (continuous), except 20A model. 20A model: 1.25 times full scale rating 50 times full scale (1 Sec. transient) Dielectric Test (Input/Output/Case)1500VAC
OUTPUT
Output Ripple
Less than 1.0%F.S.
Response
400 milliSeconds
Output Loading (¥Ø)
0-1mA
0-10K
4-20mA
0-1500
Field Adjustable Cal
¡¾10%
ACCURACY
¡¾0.25%F.S. (internal sensor)
¡¾0.5%F.S. (external sensor)
Includes effects of linearity
0.5%F.S. over frequency range (typical.)
Temperature Effect
(-20¡ÆC to 60¡ÆC)
¡¾1.0%RDG
Instrument Power (STD. 4-20mA Units)
85-135VAC, 50-70Hz