Limit Alarms are setpoint controllers that regulate industrial processes,whether discrete,etc.
Limit Alarms are setpoint controllers that regulate industrial processes, whether discrete, batch or continuous. Alarms are indicators of problems, be they production line faults, process upsets, equipment failures or control system abnormalities.
Alarm Flexibility The AP1000 Series satisfies the need for compact signal-conditioning equipment that 1) provides the flexibility of a separate, individual limit or on/off control device, 2) accepts a variety of direct sensor or transducer inputs, and 30 provides either Single-Trip, Latching or Dual-trip relay outputs.
The Action Pak 1000 Series provides many combinations of sensor input, setpoint control and relay output selection for most conventional process and industrial alarm/control applications.
Field Configurable Alarms The popular AP1000 Series Limit Alarms are field configurable. The DC input AP1080/1090, the thermocouple input AP1280/1090 and the AC input AP1690 can all be configured in the field by setting DIP switches for input range or type, alarm function (Hi/Lo) and alarm state (failsafe/non-failsafe). This minimizes spare parts inventory and provides an off the shelf solution for virtually any alarm function.
Lifetime Warranty All of the Action Pak Limit Alarms carry a lifetime warranty.
CAT NO.
MODEL
DEscRIPTION
AVAIL
PRICE
ACT3001
AP4380-2000
SETPOINT CONTROLLER, 10MV-100VDC VOLT INPUT
Yes
777,600
Input Types
DC Volt
Field Configurable Input Span, Min./Max.
10mV to 100mV* span, *Bipolar input switch for +/- 100 Deg.
Mounting Socket
8 pin
Field Configurable Output Type
DC Voltage (0-5V, 0-10V)
ACT3002
AP4390
SETPOINT CONTROLLER, 1MA-100MADC VOLT INPUT
Yes
1,080,000
Input Types
DC Volt
Field Configurable Input Span, Min./Max.
1mA to 100mA*, * Bipolar input switch for +/-100%
Mounting Socket
11 pin
Field Configurable Output Type
DC Current (0-1mA, 4-20mA)
ACT3003
AP4382
SETPOINT CONTROLLER, BIPOLAR INPUT SWITCH
Yes
777,600
Input Types
DC Volt
Field Configurable Input Span, Min./Max.
10mV to 100mV* span, 1mA to 100mA*, * Bipolar input switch for +/-100%
Mounting Socket
8 pin
Field Configurable Output Type
DC Bipolar (-5 to +5V, -10 to +10V)
ACT3004
AP1080
SETPOINT CONTROLLER, 10MV-200VDC CURR INPUT
Yes
486,000
Input Types
DC Current
Field Configurable Input Span, Min./Max.
10mV to 100mV* span, * Bipolar input switch for +/-100%
Mounting Socket
11 pin
Field Configurable Output Type
Alarm (Single DPDT Relay)
ACT3005
AP1090
SETPOINT CONTROLLER, 1-100MA DC CURRENT INPUT
Yes
648,000
Input Types
DC Current
Field Configurable Input Span, Min./Max.
1mA to 100mA*, * Bipolar input switch for +/-100%
Mounting Socket
11 pin
Field Configurable Output Type
Alarm (Dual SPDT Relay)
ACT3012
AP1290
SETPOINT CONTROLLER THERMOCOUPLE INPUT
Yes
691,200
Input Types
Thermocouple
Field Configurable Input Span, Min./Max.
B: 250 to 1320 Deg. C, E: 75 to 1000 Deg. C, J: 63 to 950 Deg. C, K: 63 to 1370 Deg. C, R/S: 100 to 1710 Deg. C, T: 63 to 550 C
Mounting Socket
11 pin
Field Configurable Output Type
Alarm (Dual SPTD Relay)
ACT03
MD03
OPTIONAL TS35 x 7.5 DIN Rail (2 meters) FOR Action Pak¢ç Limit Alarms
Yes
108,000
MD08
MD08
OPTIONAL DIN-rail mount, 8-pin socket FOR Action Pak¢ç Limit Alarms
Yes
32,400
MD11
MD11
OPTIONAL DIN-rail mount, 1-pin socket FOR Action Pak¢ç Limit Alarms
Yes
32,400
IN0 M008
M008
OPTIONAL Surface mount, 8-pin socket FOR Action Pak¢ç Limit Alarms
Yes
32,400
IN0 M011
M011
OPTIONAL Surface mount, 11-pin socket FOR Action Pak¢ç Limit Alarms