Non-interrupted Harmonic Analysis ( V and A ) to the 50th Order in % and Magnitude
Analysis of % THD-F and C.F.
Fast Peak Function (33¥ìs and 39¥ìs)
Programmable PT (1 to 250 )ratios
Auto - Power - Off : 30 Minutes
Flexible probe , different from normal clamp meter, can pass through obstacles at will and wind many conducting wires simultaneously, max. diameter 170mm
AC Watt (50 or 65 Hz, PF 0.5 to 1, CT=1) AFLEX-3005 only
Range
Resolution
Accuray of reading
100.0 - 999.9 W
0.1 W
2% of range
1.000 - 9.999 KW
0.001 KW
2% of range
10.00 - 99.99 KW
0.01 KW
2% of range
100.0 - 999.9 KW
0.1 KW
2% of range
1000 - 9999 KW
1 KW
2% of range
AC Voltage(50 or 65 Hz, ,Auto Range, True RMS)
Range
Resolution
Accuracy of reading
4.0 V - 600 V
0.1 V
¡¾0.5% ¡¾ 5dgts
Harmonics of AC Current in % and Magnitude(1 to 50th order)
Range
Resolution
Accuracy in %
Accuracy of Magnitude
1-20th
0.1%
¡¾2%
¡¾2% of reading ¡¾0.4A
21st-50th
0.1%
¡¾4% of reading ¡¾2.0%
¡¾4% of reading ¡¾ 0.4V
AC Current(50 or 65 Hz ,Auto Range, True RMS)
Range
Resolution
Accuracy of reading
0 - 300.0 A
0.1 A
1% of range
300.0 - 999.9 A
0.1 A
1% of range
1000 - 3000 A
1 A
1% of range
Harmonics of AC Voltage in % and Magnitude(1 to 50th order)
Range
Resolution
Accuracy in %
Accuracy of Magnitude
1-20th
0.1%
¡¾2%
¡¾2% ¡¾0.5V
21st-50th
0.1%
¡¾4% of reading ¡¾2.0%
¡¾4% of reading ¡¾ 0.5V
Total Harmonics Distortion(%THD-F,1 to 50th order)