Tune burners to optimize efficiency. Enhance safety and environmental quality. Monitor efficiency |
Features |
- Tune burners to optimize efficiency
- Enhance safety and environmental quality
- Monitor efficiency
- Measure safety and emissions gases
- Supplement preventative maintenance
|
| | SPECIFICATIONS
Oxygen (O2)* |
0 to 25% |
Carbon Monoxide (CO) |
0 to 10,000 (1%) |
Carbon Monoxide (CO)– H2 Compensated* |
0 to 5,000 ppm |
Carbon Monoxide (CO)– High Concentration* |
0 to 20,000 ppm (2%) |
Nitric Oxide (NO)* |
0 to 4,000 ppm |
Sulfur Dioxide (SO2)* |
0 to 4,000 ppm |
Nitrogen Dioxide (NO2)* |
0 to 500 ppm |
Carbon Dioxide (CO2) |
Calculated from O2 and fuel type |
Excess Air (%EA) |
0 to 1,000% |
Efficiency (Enet and Egr) |
0 to 125% |
Stack Loss |
0 to 100% |
Supply Temperature |
-22 to 392¡ÆF (-30 to 200¡ÆC) |
Flue Gas Temperature |
32 to 1,800¡ÆF (0 to 1,000¡ÆC) |
Draft |
¡¾30 in. H2O (¡¾80mBar) |
General Instrument Data: |
Operating Temperature |
32 to 122¡ÆF (0 to 45¡ÆC) |
Storage Temperature |
-20 to 140¡ÆF (-30 to 60¡ÆC) |
Max. Probe Temp. |
1,800¡ÆF (1,000¡ÆC) |
Instrument Humidity Range |
|
Continuous |
15 to 90%, 0 to 99% Intermittent |
See selection chart for model configurations .*Electrochemical Sensor |
Model |
Series A |
Series B |
Series C |
Series D |
Series E |
Series F |
Series G |
Series H |
Carbon Monoxide |
X |
|
|
|
|
C |
X |
|
Oxygen |
|
X |
|
|
|
|
|
X |
Nitric Oxide |
|
|
X |
|
|
|
|
¡¡ |
Nitrogen Dioxide |
|
|
|
X |
|
|
|
¡¡ |
NOx |
|
|
|
|
|
|
|
¡¡ |
Sulfur Dioxide |
|
|
|
|
X |
|
|
¡¡ |
Carbon Dioxide* |
|
|
|
|
|
|
|
X |
Ambient and Stack Temperatures |
|
|
|
|
¡¡ |
¡¡ |
|
X |
Draft Pressure |
|
|
|
|
|
|
X |
|
Efficiency (Loss) (qA) |
|
|
|
|
|
|
|
X |
Excess Air (¥ë) |
|
|
|
|
|
|
|
X |
Data Storage/ Review/Print |
|
|
|
¡¡ |
|
|
X |
X |
User-Defined Fuels |
|
|
|
|
|
|
|
X |
Battery Life (hrs) |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
AC Power |
|
|
|
|
|
|
X |
X |
Field Replaceable Sensors |
X |
X |
X |
X |
X |
X |
X |
X |
Field Calibration |
X |
X |
X |
X |
X |
X |
X |
X |
*Calculated from fuel type and O2 C High Concentration H Hydrogen compensated |
Model |
Series I |
Series J |
Series K |
Series L |
Series M |
Series N |
Series O |
Series P |
Series Q |
Series R |
Carbon Monoxide |
X |
X |
H |
H |
H |
H,C |
H |
H,C |
H |
H |
Oxygen |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Nitric Oxide |
|
|
X |
|
X |
|
X |
X |
X |
|
Nitrogen Dioxide |
|
|
|
|
|
|
|
|
X |
X |
NOx |
|
|
X |
|
X |
|
X |
X |
X |
|
Sulfur Dioxide |
|
|
|
|
|
|
X |
|
|
X |
Carbon Dioxide* |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Ambient and Stack Temperatures |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Draft Pressure |
|
X |
X |
X |
X |
X |
X |
X |
X |
X |
Efficiency (Loss) (qA) |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Excess Air (¥ë) |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Data Storage/ Review/Print |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
User-Defined Fuels |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Battery Life (hrs) |
10 |
10 |
24 |
24 |
24 |
24 |
24 |
24 |
24 |
24 |
AC Power |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Field Replaceable Sensors |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
Field Calibration |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
*Calculated from fuel type and O2 C High Concentration H Hydrogen compensated |
CAT NO. |
|
MODEL |
|
DEscRIPTION |
|
AVAIL |
|
PRICE |
TS145317 |
|
CA-6010 |
|
Single Gas Monitor with CO Sensor, Series A |
|
Yes |
|
982,800 |
TS145318 |
|
CA-6020 |
|
Single Gas Monitor with O2 Sensor, Series B |
|
Yes |
|
1,069,200 |
TS145319 |
|
CA-6030 |
|
Single Gas Monitor with NO Sensor, Series C |
|
Yes |
|
1,717,200 |
TS145320 |
|
CA-6040 |
|
Single Gas Monitor with NO2 Sensor, Series D |
|
Yes |
|
1,717,200 |
TS145321 |
|
CA-6050 |
|
Single Gas Monitor with SO2 Sensor, Series E |
|
Yes |
|
1,717,200 |
TS145322 |
|
CA-6060 |
|
Single Gas Monitor with HI-CO Sensor, Series F |
|
Yes |
|
1,717,200 |
TS145323 |
|
CA-670 |
|
Combustion Analyzer with CO Sensor, Series G |
|
Yes |
|
1,242,000 |
TS145324 |
|
CA-6120 |
|
Combustion Analyzer with O2 Sensor, Series H |
|
Yes |
|
1,285,200 |
TS145325 |
|
CA-6130 |
|
Combustion Analyzer with CO, O2, CO2 Sensors, Series I |
|
Yes |
|
1,674,000 |
TS145326 |
|
CA-6140 |
|
Combustion Analyzer with CO, O2, CO2 Sensors, Series J |
|
Yes |
|
1,933,200 |
TS145327 |
|
CA-6203 |
|
Combustion Analyzer with CO, O2, NO, NOX Sensors, Series K |
|
Yes |
|
3,229,200 |
TS145304 |
|
CA-6210 |
|
CA-CALC with O2 and CO Sensors |
|
Yes |
|
4,741,200 |
TS145305 |
|
CA-6211 |
|
CA-CALC with O2 and NO Sensors |
|
Yes |
|
6,037,200 |
TS145306 |
|
CA-6212 |
|
CA-CALC with O2 and High Concentration CO Sensors |
|
Yes |
|
6,037,200 |
TS145307 |
|
CA-6213 |
|
CA-CALC with O2, CO, NO and SO2 Sensors (includes Teflon-lined sampling probe) |
|
Yes |
|
7,765,200
|
TS145308 |
|
CA-6214 |
|
CA-CALC with O2, NO and High Concentration CO Sensors |
|
Yes |
|
7,765,200 |
TS145309 |
|
CA-6215 |
|
CA-CALC with O2, CO, NO and NO2 Sensors (includes Teflon-lined sampling probe) |
|
Yes |
|
7,765,200
|
TS145316 |
|
CA-6216 |
|
Combustion Analyzer with O2, NO, SO2, CO2 Sensors, Series R |
|
Yes |
|
7,765,200 | | |
|
|
| |
|
¹øÈ£ |
Á¦¸ñ |
ÀÛ¼ºÀÚ |
ÀÛ¼ºÀÏ |
Æò°¡Á¡¼ö |
|
|
|
ÀÌ »óÇ°¿¡ ´ëÇÑ »ç¿ëÈıⰡ ¾ÆÁ÷ ¾ø½À´Ï´Ù.
»ç¿ëÈı⸦ ÀÛ¼ºÇØ ÁÖ½Ã¸é ´Ù¸¥ ºÐµé²² ¸¹Àº µµ¿òÀÌ µË´Ï´Ù. |
|
|
|
|
|
|
| |
|
¹øÈ£ |
Á¦¸ñ |
ÀÛ¼ºÀÚ |
ÀÛ¼ºÀÏ |
´äº¯ |
|
|
|
ÀÌ »óÇ°¿¡ ´ëÇÑ Áú¹®ÀÌ ¾ÆÁ÷ ¾ø½À´Ï´Ù.
±Ã±ÝÇϽŠ»çÇ×Àº ÀÌ°÷¿¡ Áú¹®ÇÏ¿© ÁֽʽÿÀ. |
|
|
|
|
|
|
| |
ÀÌ »óÇ°°ú °ü·ÃµÈ »óÇ°ÀÌ ¾ø½À´Ï´Ù. | |
|
|