Insulation Resistance Tester produces 10 kV test voltages to meet IEEE43-2000 Requirements
The new IEEE Standard 43-2000 entitled "IEEE recommended PRACTICE FOR testing Insulation Resistance of rotating Machines recommends using a 10 kV test voltage for motor windings rated greater than 12 kV." Additionally, the Polarization Index test is recommended. Designed to perform these tests in the insulation testing of : • Generators • Winding Motors • Traction Motors • Fan Motors
Valuable in industries such as: • Steel Manufacturing • Railroad and Mining • Electrical Power Generation • Rewind Shop • Heavy Industry
Features
Operates on internal rechargeable batteries or an AC supply
5 Voltage Ranges: 500, 1000, 2500, 5000, 10,000 Volts
Insulation Resistance Measurements to 500 GW 1 TW analog
Automatic Polarization Index Test
Data Storage and Downloading
Integral timer
IP54 Rating
Interference Rejection of 1 mA RMS per kV to a max. of 2 mA
Humidity Specification of 90% R.H. @ 40¡ÆC (104¡ÆF) maximum
SPECIFICATIONS
Dimensions
15 1/4 (385mm) x 10 1/2 (265mm) x 9 3/4 (250mm)
Weight
15 1/4 lb (7kg) approx.
Instrument Protection
IP54 with case closed
Safety
Meets EN61010-1; 2001 for operation at ¡Â 2000 m above sea level
EMC
Meets EN61326-1:1998 for use in areas other than domestic
Test Voltages (d.c.)
500V, 1000V, 2500V, 5000V, 10000V
Test Voltage accuracy
¡¾ 5 % on 100¥Ø W loads and above
Insulation Resistance Ranges
Digital
10 k ¥Ø to 50 G ¥Ø @ 500 V; 10 k ¥Ø to 100 G ¥Ø @ 1000 V 10 k ¥Ø to 250 G ¥Ø @ 2500 V; 10 k ¥Ø to 500 G¥Ø @ 5000 V 10 k ¥Ø to 500 G ¥Ø @ 10000 V
Analog
100 k ¥Ø to 1T ¥Ø @ all voltages
Accuracy (at 23¡Æ C)
¡¾ 5 % on 100 M ¥Ø load
Basic Accuracy
¡¾ 5 % of reading 10 M ¥Ø to 100G¥Ø all voltages
Current Range
0.01 nA to 999 ¥ìA
Accuracy (23 deg C)
¡¾ 5 % ¡¾ 1nA on 100 M¥Ø load
Basic Accuracy
¡¾ 5 % of reading 10M ¥Ø 100 G¥Ø all voltages
Guard
2% error guarding 500 k ¥Ø leakage with 100M¥Ø load
Short Circuit Current
5mA nominal
Voltmeter Range
50 to 1000V dc or ac
Accuracy (at 23¡Æ C)
¡¾ 2 % ¡¾ 1V
Interference Rejection
1mA RMS per kV to a maximum of 2mA
Capacitor Discharge Time
<2 s per ¥ìF to discharge from 10kV to 50V
Timer
0:00 to 99:59 minutes. Can be set to stop test after time limit or run indefinitely
Instrument Display
3 digit LCD Analog/Digital
Power Supply
Battery or Line Powered; Rechargeable lead-acid batteries (12,V 4Ah), or 100V to 240VAC, 50/60 Hz supply
Battery Life
Typically 4 hrs. continuous testing @ 10kV; Full charge in approximately 12 hrs
Temperature Range
Operating: -20¡Æ C to +50¡ÆC (-4¡Æ F to + 122¡Æ F); Storage: -25¡Æ C to + 65¡ÆC (-12¡Æ F to + 149¡Æ F)
Temperature Coefficient
¡¾0.1% per ¡ÆC over the test voltage for the temperature range 0¡Æ C to +30¡ÆC (+ 9.06% per ¡ÆF)
Humidity
90% RH @ 40¡Æ C (104¡Æ F) max.
CAT NO.
MODEL
DEscRIPTION
AVAIL
PRICE
BD21001
MEG10-01
10 kV Insulation Tester; includes test leads, RS232 cable, User Guide, Download Manager CD-ROM, Quick Start Guide, Power Cord