Power supply: from network 230 V or 115 V +15%-20% @ 35¡À400 Hz (4 VA).
Display: reverse red LCD with LED backlight
Voltmeter inputs: VL1, VL2, VL3, N up to 430 V phase-neutral, 750 V phase-to-phase, 35¡À400 Hz
Voltmeter input impedance: 2 Mohm
Voltage input overload: max 850 V phase-neutral
Current inputs: AL1, AL2, AL3, COM. , consumption 1 VA. Three or two 5A external curr.transf. required
Measuring range : 0-120% In
Sensitivity: current 20 mA ; voltage 10 mV
Overcurrent :withstand 10 amps permanently.
Number of scales: 1 voltage scale, 2 current scales
Measurements: True R.M.S. up to25th harmonic = 1250Hz with fundamental @50 Hz
Sampling frequency: 2.5 kHz.
Accuracy: <0.5% for Voltage and current and Power
Connection: Single phase or three phase star, three phase delta, or diphase systems
Weight : 0.6 Kg
Protection level: instrument IP20, front panel IP40
Temperature range: -10¡ÆC ¡À + 50¡ÆC
Relative humidity range :(R.H.): from 20% to 90%.
Condensation: non condensing.