Simple on-line trip frequency setting, User settable trip frequency from 0.1 Hz to 25 KHz
Features
  • Simple on-line trip frequency setting
  • User settable trip frequency from 0.1 Hz to 25 KHz
  • Over-speed, Under-speed, and Zero-speed Detection
  • Relay latching, alarm override, and alarm reset functions
  • Programmable input circuit accepts variety of sensor outputs
  • Hysteresis and offset functions available
  • 85 to 250 VAC and 9 to 32 VDC versions available
  • Input and relay status indication LED¡¯s
  • UL/CUL Recognized Component
 
SPECIFICATIONS

Power

AC Powered Versions: 85 to 250 VAC; 48 to 62 Hz; 5.5 VA

DC Powered Versions: 9 to 32 VDC; 2.0 W

Power Up Current

Ip = 600 mA for 50 msec max.

Sensor Power

(AC version only) +12 VDC ?25% @ 60 mA max.

Operating Frequency Range

0 Hz to 25 KHz

Signal Input

DIP switch selectable to accept signals from a variety of sources, including switch contacts, outputs from CMOS or TTL circuits, magnetic pickups, and all standard RLC sensors.

Current Sourcing

Internal 1 K. pull-down resistor for sensors with current sourcing output.

(Max. sensor output current = 12 mA @ 12 V output.)

Current Sinking

Internal 3.9 K. pull-up resistor for sensors with current sinking output.

(Max. sensor current = 3 mA.)

Low Bias

Input trigger levers VIL = 0.25 V, VIH = 0.75 V; for increased sensitivity when used with magnetic pickups.

Hi Bias

Input trigger levels VIL = 2.5 V, VIH = 3.0 V; for logic level signals.

Max. Input Signal

¡¾90 V; 2.75 mA max.

(with both Current Sourcing and Current Sinking resistors switched off).

Environmental Conditions

Operating Range: 0 to 50¡ÆC

Certifications and Compliances Safety

UL Recognized Component, File #E137808, UL508, CSA 22.2 No. 14
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
IECEE CB Scheme Test Certificate # UL1683A-176645/USA, CB Scheme Test Report
# 97ME50135-042297 Issued by Underwriters Laboratories, Inc. IEC 1010-1, EN 61010-1
Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1.

Electromagnetic Compatibility

Immunity to EN 50082-2

Emissions to EN 50081-2


CAT NO. MODEL DEscRIPTION AVAIL PRICE
RLIFMR0036   IFMR   DIN Rail Mount Speed Switch   Yes   300,240
Output: 1 SPDT 5A Relay, Power: 9 – 32V DC
RLIFMR0066   IFMR   DIN Rail Mount Speed Switch   Yes   300,240
Outputs: 1 SPDT 5A Relay, Power: 85 – 250V AC